| CARVIEW |
CALIBRATE
YOUR POWER
Professional electrical engineering utility. Now featuring reverse wire sizing, parallel run calculation, and power factor correction.
System Logs
> Calculating load: 0.00 A (Derived)
> Phase configuration: 1-Phase
> Correction factor: 1 PF
> Parallel sets: 1
Understanding Voltage Drop
Master the essential concepts behind voltage drop calculations and why they matter for every electrical installation.
What is Voltage Drop?
Voltage drop is the reduction in electrical potential along a conductor carrying current. As electrons flow through wire, they encounter resistance, converting electrical energy to heat and reducing the voltage available at the load end.
Learn MoreThe Core Formula
For single-phase circuits: Vd = 2 × I × L × R / 1000. For three-phase: Vd = √3 × I × L × R / 1000. Understanding these formulas is fundamental to proper wire sizing.
NEC Requirements
The National Electrical Code recommends maximum 3% voltage drop for branch circuits and 5% total (feeder + branch). While informational, following these limits ensures optimal equipment performance and energy efficiency.
NEC StandardsFactors Affecting Drop
Multiple factors influence voltage drop: conductor material (copper vs aluminum), wire gauge (AWG/kcmil), circuit length, load current, temperature, and whether it's AC or DC. Each must be considered for accurate calculations.
Explore FactorsWhy It Matters
Excessive voltage drop causes motor overheating, dim lighting, equipment malfunction, and energy waste. In critical systems like data centers or medical facilities, proper voltage is essential for reliable operation.
Read MoreAC vs DC Systems
DC systems use pure resistance calculations, while AC systems must account for impedance including reactance. Three-phase AC uses √3 multiplier instead of 2. Power factor also affects AC voltage drop in inductive loads.
Compare SystemsProfessional Design Approach
Our calculation methodology follows IEEE and NEC standards, providing engineers with reliable data for critical decisions. Every calculation considers real-world factors that affect conductor performance.
NEC Chapter 9 Table 8
Resistance values derived from official NEC tables for both copper and aluminum conductors at 75°C.
Temperature Compensation
Adjustments for ambient temperature effects on conductor resistance using standard coefficients.
Power Factor Correction
AC calculations include power factor for accurate voltage drop in inductive and capacitive loads.
Parallel Conductor Support
Calculate effective resistance for parallel conductor sets, essential for high-current applications.
Calculation Reference
Code Compliance Standards
The National Electrical Code (NEC) provides guidelines for maximum allowable voltage drop to ensure safe and efficient electrical installations. While these are recommendations rather than requirements, following them is considered best practice.
Maximum recommended drop from panel to outlet (NEC 210.19(A) Informational Note No. 4)
Combined feeder and branch circuit drop from service to final outlet
Important Notes
- •Voltage drop limits are informational notes, not code requirements
- •Some jurisdictions adopt stricter requirements
- •Motor circuits may require lower drop for starting
- •Sensitive electronics often need tighter tolerances
- •Always verify with local codes and AHJ requirements
Common Use Cases
From residential installations to industrial power distribution, voltage drop calculations are essential across all electrical applications.
Residential
Long runs to detached garages, workshops, and outdoor lighting. Sub-panel feeders and EV charger installations.
View Cases →Industrial
Motor feeder circuits, MCC installations, long factory runs, and high-current distribution systems.
View Cases →Solar & Renewable
PV string wiring, DC combiner to inverter runs, and battery storage system connections.
View Cases →Commercial
HVAC equipment feeders, lighting circuits, data center power, and tenant distribution.
View Cases →Frequently Asked Questions
Get answers to common questions about voltage drop calculations, wire sizing, and electrical design best practices.
Full Knowledge BaseWhat causes voltage drop in electrical circuits?
How do I calculate voltage drop for three-phase systems?
What's the difference between copper and aluminum for voltage drop?
When should I use parallel conductors?
How does power factor affect voltage drop?
Ready to Calculate?
Use our professional voltage drop calculator above to ensure your electrical installations meet NEC guidelines and perform optimally.
Methodology
Calculations derived from NEC Chapter 9 Table 8. AC calculations assume effective Z approximation derived from DC resistance adjusted for power factor. For large steel conduit runs (>4/0 AWG), impedance may be higher.
Limits
- Branch 3%
- Feeders 3%
- Total 5%